Installation and construction requirements for explosion-proof lighting fixtures

SINO Testing Services

| 2020-11-02|Return

Explosion proof lighting fixtures are common explosion-proof electrical equipment, and their presence can be seen in many explosive hazardous areas. As a special lighting fixture, its installation, use, maintenance, replacement, and construction must comply with the requirements of relevant national explosion-proof standards to ensure its explosion-proof performance and the safety of the location.

What are the technical requirements for installing and replacing explosion-proof lamps in explosive hazardous areas?

The selection of explosion-proof lamps should be considered according to the installation siteEPLLevel and equipment category. If different power light sources can be used, the possibility of temperature group changes should be considered. Trigger for metal halide lamps, high-pressure sodium lamps, etcexplosion-proofAfter the bulb of the lamp is damaged, it should be replaced in a timely manner. Otherwise, the trigger in the entire circuit will mistakenly believe that the bulb is not lit and continuously emit high voltage triggers, resulting in long-term continuous high voltage burning of components such as ballasts, triggers, capacitors, etc.

The type, model, and power of explosion-proof lamps should meet the requirements of design and product technical conditions, and cannot be changed arbitrarily. When replacing the light bulb of the lighting device, the correct bulb rating and model should be used, otherwise it may cause excessive temperature. In places where color identification is required (such as on-site maintenance of large unit equipment), explosion-proof floodlights can be used, with metal halide lamps as the light source and a rated power of up to1000W.

Due to the special structure, explosion-proof lamps have higher sealing performance than ordinary lamps, and the temperature rise generated during operation can easily affect the service life of the components. Confirm to replace the bulb before or when the rated lifespan is reached; Exceeding the rated lifespan reduces light output, increases energy consumption, and increases the likelihood of lamp breakage.

The emergency power supply of emergency explosion-proof lamps should be fully discharged before use, and then charged once24Normal use can only be entered after hours, otherwise it will reduce the battery's storage capacity. The emergency device must be charged and discharged every three months. The working voltage for the normal operation of explosion-proof lamps should be stable at220Soil5%VBetween them, frequent fluctuations are not allowed, otherwise it is easy to burn out the lighting components. If conditions permit, it is best to configure a regulated power supply.

The original rubber sealing ring and retaining ring of the explosion-proof lamp are accessories that ensure the sealing of the lamp's wires and cables when it leaves the factory. They cannot be omitted or discarded, and cannot be replaced arbitrarily, otherwise it will damage the overall explosion-proof function of the lamp. The sealed part of the lamp should not be disassembled and opened frequently.

When selecting light sources and ballasts, attention should be paid to uniform model specifications. Inconsistencies may cause functional impairment or damage. It is recommended to choose well-known brands. If the light source is damaged, it should be turned off and replaced in a timely manner. After the ignition of light sources such as metal halide lamps and high-pressure sodium lamps is turned off or extinguished, they must be cooled for fifteen minutes until the temperature of the light source drops before the power can be turned on and restarted. Hot start can easily damage or burn out the light source.

Working in a continuous operation system(24Hours/day,7All kinds of light sources in the day/week should be turned off once a week, at least once a week15-30minute. If this operation is not followed, it will increase the possibility of light source rupture and affect the lifespan of the light source. After the installation of explosion-proof lamps is completed, the insulation resistance between the pole and the shell should be checked for normality when delivering them. Explosion proof lamps should be stored in well ventilated areas with no dripping or liquid intrusion, and the air humidity should not exceed90% ,The temperature is not higher than40℃, not less than25℃In the warehouse, and the storage period shall not exceed one year.


The copyright of this article belongs to Zhongnuo Testing. Plagiarism and theft will be pursued, and reprinting must indicate the original source.



Related Recommendations
Contact us
0755-2102 2109
Add: 13F, Building C, Kangjia Guangming Technology Center, No. 288 Xingxin Road, Guangming District, Shenzhen
Follow us
Copyright: Shenzhen Zhongnuo Testing Technology Co., Ltd. 粵ICP備18004888號
Service Hotline
18924609560
點擊這里給我發消息 1354407946
點擊這里給我發消息 1354407946
主站蜘蛛池模板: 中文字幕 日本 | 亚洲国产精品久久久久婷婷老年 | 国产jjizz一区二区三区视频 | 欧美18一19sex性护士农村 | 黄网站在线免费看 | 日韩av手机在线免费观看 | 久久国产28 | 深夜免费视频 | 91在线色| 福利四区| 日韩在线播放第一页 | 国内成人自拍视频 | 手机在线看片国产 | 国产91在线播放九色 | 天天夜夜操操 | 天天操天天碰 | 91网站链接 | 免费毛片随便看 | 亚洲视频在线观看免费视频 | 久久久久久久久久久高潮一区二区 | 欧美一级做a| 羞羞羞网站| 一级电影免费看 | 日日噜噜噜噜久久久精品毛片 | 精品欧美一区二区精品久久小说 | 欧美国产成人在线 | 成人毛片av在线 | 精品国产一区二区久久 | 亚洲第九十九页 | 国产乱淫av片免费 | 青青草成人免费视频在线 | 黄色网络免费看 | 精品国产九九九 | 国产亚洲高清视频 | 久久恋| 久久久www成人免费毛片 | 激情综合在线观看 | 久久精品99国产国产精 | 视频一区二区三区在线播放 | 日韩黄色免费电影 | 国产精品久久久久一区二区 |